• Xoba UL 2808 Split Core Current Transformer Xh-Sct-0750
  • Xoba UL 2808 Split Core Current Transformer Xh-Sct-0750
  • Xoba UL 2808 Split Core Current Transformer Xh-Sct-0750

Xoba UL 2808 Split Core Current Transformer Xh-Sct-0750

Application: Electronic, Instrument, Position Sensor, Audio, Lighting
Type: Split Core Current Transformer
Phase: Single
Operation Condition: Indoor
Usage: Measurement
Winding Form: Multilayer Honeycomb Type
Samples:
US$ 0/Piece 1 Piece(Min.Order)
| Request Sample
Customization:
Diamond Member Since 2009

Suppliers with verified business licenses

Rating: 5.0/5
Manufacturer/Factory

Basic Info.

Model NO.
XH-SCT-0750
Insulating Medium
Epoxy Resin
Installation
Active Type
Magnetic Circuit Structure
Combined Type
Voltage Transformation Principle
Capacitive Type
Model
Split Core Current Transformer
Output
0.33V or Ma
Certificates
UL,ETL,CE,RoHS
Transport Package
Outer Carton with Smaller Inner Box
Specification
UL, ROHS, ISO9001: 2008
Trademark
Jiangyin spark
Origin
China(Mainland)
HS Code
8504
Production Capacity
200, 000 PCS/Month

Product Description

Split core Current Transformer SCT XOBA 333mV Secondary  
The JIANGYIN SPARK series of split core current transformer are designed for fast and easy installation.The split core design permits non-contact current measurements through magnetic field induction without requiring that the primary wire be taken offline and disconnected for CT installation.This method permits a safer,easy and portable current measurement. An internal precision burden resistor across the secondary winding of the CT provides a safe low voltage output and permits safe opening of the secondary

Features
,SPECIFICATIONS :
1,Rated Voltage:0.66KV;
2,Insulation Voltage:5400V
CATIII 600V or CATIV 250V
3,Rated Frequency:50HZ or 60HZ;
4,Operating Temperature:-40ºC to +55ºC;
5,Flame resistance:UL94-V0;
6,Leads:20ft (6m) UL 1015 18awg
7,Certificates:UL2808 and IEC61010-1


Application
Measures AC current flow to electric motors, lighting, air conditioning equipment, etc.Compatible with HVAC temperature control, power management,building automation systems.

Model
I. D. Rated Amps Output Accuracy SIZE( mm )
A B C D E
XH-SCT-0750 0.75"
(19.1mm)
5, 15, 30, 50, 70, 100, 150, 200 0.333V 1.0 51.6 54.1 16.6 19.1 18
XH-SCT-1250 1.25"
(31.8mm)
70, 100, 150, 200, 250, 300, 400, 600 1.0 82.3 85.3 26.4 32 32.3
XH-SCT-2000 2.00"
(50.8mm)
400, 600, 800, 1000, 1200 1.0 120 125 29.6 52.5 52
XH-SCT-3000 3.00" x 5.00"
(76.2mm x127mm)
1000, 1200, 1500, 2000.3000 1.0 145 199 30.5 76 130

Drawing of split core CTs XH-sct-0750

Xoba UL 2808 Split Core Current Transformer Xh-Sct-0750

Performance of split core CTs XH-sct-0750
Xoba UL 2808 Split Core Current Transformer Xh-Sct-0750
Our hot sales:
Xoba UL 2808 Split Core Current Transformer Xh-Sct-0750


 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now