Split core Current Transformer SCT XOBA 333mV Secondary
The JIANGYIN SPARK series of split core current transformer are designed for fast and easy installation.The split core design permits non-contact current measurements through magnetic field induction without requiring that the primary wire be taken offline and disconnected for CT installation.This method permits a safer,easy and portable current measurement. An internal precision burden resistor across the secondary winding of the CT provides a safe low voltage output and permits safe opening of the secondary
Specification of Jiangyin Spark clamp ct split core current transformer
Rated Current 5A to 3000A loads.
Rated output: 0.333VAC
Accuracy: ± 1% from 5% to 120% of rated current
Phase Angle: Less than 2 degrees at 50% of rated current
Insulation Voltage: 600VAC
Maximum Primary Voltage: 5000VAC(Insulated Conductor)
Operating Temperature: -15Cto 60C.
Frequency Range: 50-400Hz
Leads: 4Foot(105cm), UL 1015, Twisted Pair,
0.34 mm2(22AWG)
UL&CE recognized. RoHS Compliant
Output and leads can be customized
Application
Measures AC current flow to electric motors, lighting, air conditioning equipment, etc.Compatible with HVAC temperature control, power management,
Residential Systems
Model |
I. D. |
Rated Amps |
Output |
Accuracy |
SIZE ( mm ) |
A |
B |
C |
D |
E |
XH-SCT-0750 |
0.75"
(19.1mm) |
5, 15, 30, 50, 70, 100, 150, 200 |
0.333V |
1.0 |
51.6 |
54.1 |
16.6 |
19.1 |
18 |
XH-SCT-1250 |
1.25"
(31.8mm) |
70, 100, 150, 200, 250, 300, 400, 600 |
1.0 |
82.3 |
85.3 |
26.4 |
32 |
32.3 |
XH-SCT-2000 |
2.00"
(50.8mm) |
400, 600, 800, 1000, 1200, 1500 |
1.0 |
120 |
125 |
29.6 |
52.5 |
52 |
XH-SCT-3000 |
3.00" x 5.00"
(76.2mm x127mm) |
1000, 1200, 1500, 2000.3000 |
1.0 |
145 |
199 |
30.5 |
76 |
130 |
Performance of split core CTs XH-sct-0750
Wiring and test of split core current transformer:
Package of split core current transformer: